首页 | 本学科首页   官方微博 | 高级检索  
     

一起110kV电缆中间接头故障分析
引用本文:陈腾彪,邬韬,罗致远,吴彦志. 一起110kV电缆中间接头故障分析[J]. 企业科技与发展, 2012, 0(10): 62-64
作者姓名:陈腾彪  邬韬  罗致远  吴彦志
作者单位:深圳供电局有限公司,广东深圳,518020
摘    要:通过对发生故障的110 kV电缆中间接头进行解剖,分析推断故障原因可能是绝缘层与半导电屏蔽层间存在微小气隙缺陷,经长期运行发生局部放电并发展成贯穿性导电通道造成绝缘击穿,提出采取在线局部放电测试的方法对设备健康状态进行监控,及时发现缺陷并予以消缺,防止故障发生.

关 键 词:电缆中间接头  故障分析  监控

110kV Cable Joints Failure Analysis
CHEN Teng-biao , WU Tao , LUO Zhi-yuan , WU Yan-zhi. 110kV Cable Joints Failure Analysis[J]. , 2012, 0(10): 62-64
Authors:CHEN Teng-biao    WU Tao    LUO Zhi-yuan    WU Yan-zhi
Affiliation:(Shenzhen Power Supply Bureau Co.,Ltd.,Shenzhen Guangdong 518020)
Abstract:Based on the failed 110 kV cable intermediate joint anatomy,the paper analyzes and deduces the failures that may be caused by the insulating layer and the inner semi-conductive shielding layer between the small air gap defect for a long time,partial discharges,which develop into through the conductive channel to cause the breakdown,and proposes on-line partial discharge test methods for equipment healthy condition monitoring,timely detection of defects and to eliminate and prevent faults.
Keywords:cable intermediate joint  failure analysis  monitoring